Origin and Uses
The OPC Specification was based on the OLE, COM, and DCOM technologies developed by Microsoft for the Microsoft Windows operating system family. The specification defined a standard set of objects, interfaces and methods for use in process control and manufacturing automation applications to facilitate interoperability.
OPC was designed to bridge Windows based applications and process control hardware and software applications. It is an open standard that permits a consistent method of accessing field data from plant floor devices. This method remains the same regardless of the type and source of data.
OPC servers provide a method for many different software packages to access data from a process control device, such as a PLC or DCS. Traditionally, any time a package needed access to data from a device, a custom interface, or driver, had to be written. The purpose of OPC is to define a common interface that is written once and then reused by any business, SCADA, HMI, or custom software packages.
Once an OPC server is written for a particular device, it can be reused by any application that is able to act as an OPC client. OPC servers use Microsoft’s OLE technology (also known as the Component Object Model, or COM) to communicate with clients. COM technology permits a standard for real-time information exchange between software applications and process hardware to be defined.
Future
The OPC Unified Architecture (UA) has been specified and is being tested and implemented through its Early Adopters program. It can be implemented with Java, Microsoft .NET, or C, eliminating the need to use a Microsoft Windows based platform of earlier OPC versions. UA combines the functionality of the existing OPC interfaces with new technologies such as XML and Web Services to deliver higher level MES and ERP support. It looks to become the standard for exchanging industrial data, replacing FactoryTalk, Archestra, some Modbus applications, and OPCDA.